Adjustable relative humidity
Change-over contact
High switching capacity
Easily accessible terminals
Clip fixing
The electronic thermostat is used for controlling heating and cooling equipment, filter fans or signal devices. The thermostat registers the surrounding air and can switch both inductive and resistive loads via snap-action contact. Functionality: The temperature setting on the scale equals to the upper switch point, which means that the NC contact opens. The temperature setting minus switch temperature difference (and tolerances) equals to the lower switch point, which means that the NC contact closes.
Technical Data
NT 82-F | |
Switch difference¹ | +/-5% RH |
Permissible air velocity | 15m/sec. |
Contact type | change-over contact |
Service life | >50,000 cycles |
Min. switching capacity | 20VAC / DC 100mA |
Max. switching capacity | 250VAC, 5A / DC 20W |
Connection | 3-pole terminal for 2.5mm², clamping torque 0.5Nm max.: rigid wire 2.5mm² (AWG 14); stranded wire² 1.5mm² (AWG 16) |
Mounting | clip for 35mm DIN rail, EN 60715 |
Casing | plastic according to UL94 V-0, light grey |
Dimensions | 67 x 50 x 38mm |
Weight | approx. 60g |
Fitting position | variable |
Operating/Storage temperature | 0 to +60°C (+32 to +140°F) / -40 to +60°C (-40 to +140°F) |
Operating/Storage humidity | max. 90% RH (non-condensing) |
Protection type | IP20 |
¹ at 50% RH
² When connecting with stranded wires, wire end ferrules must be used.
Art. No. Contact breaker (NC | Setting Range | Operating Voltage |
82HF01 | 35 to 95% RH | 20VAC/DC, 250VAC |